About product

FG Wilson P88-3

£10,683+VAT

This FG Wilson P88-3 is ideal for the UK market and includes a Perkins engine, PW1.1+ control panel, Leroy Somer alternator, all housed within a CAE canopy. 

This stock item comes with additional features including:

  • CE Certification
  • Engine Heater
  • Battery Charger
  • Bunded Tank - a duel wall fuel tank offering 110% containment to protect against spills
Request a quote Request a quote
Generator Set Specifications
Minimum Rating 80.0 kVA / 64.0 kW
Maximum Rating 100.0 kVA / 80.0 kW
Emissions/Fuel Strategy Fuel Optimised
50 Hz Prime 80.0 kVA / 64.0 kW
50 Hz Standby 88.0 kVA / 70.4 kW
60 Hz Prime 90.0 kVA / 72.0 kW
60 Hz Standby 100.0 kVA / 80.0 kW
Frequency 50 / 60 Hz
Speed 1500 or 1800 RPM
Voltage 110-480 Volts
50 Hz Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
60 Hz Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
50 Hz Standby Rating Standard reference conditions 25�C (77�F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Engine Specifications
Engine Model Perkins® 1104A-44TG2
Bore 105 mm (4.1 in)
Stroke 127 mm (5 in)
Governor Type Mechanical
Displacement 4.4l (268.5 cu. in)
Compression Ratio 17.25:1

Enquire about the P88-3